Energies Involved
The energy released in a static electricity discharge may vary over a wide range. The energy in joules can be calculated from the capacitance (C) of the object and the static potential V in volts (V) by the formula E = ½CV2. One experimenter estimates the capacitance of the human body as high as 400 picofarads, and a charge of 50,000 volts, discharged e.g. during touching a charged car, creating a spark with energy of 500 millijoules. Another estimate is 100–300 pF and 20,000 volts, producing a maximum energy of 60 mJ. IEC 479-2:1987 states that a discharge with energy greater than 5000 mJ is a direct serious risk to human health. IEC 60065 states that consumer products cannot discharge more than 350 mJ into a person.
The maximum potential is limited to about 35–40 kV, due to corona discharge dissipating the charge at higher potentials. Potentials below 3000 volts are not typically detectable by humans. Maximum potential commonly achieved on human body range between 1 and 10 kV, though in optimal conditions as high as 20–25 kV can be reached. Low relative humidity increases the charge buildup; walking 20 feet (6.1 m) on vinyl floor at 15% relative humidity causes buildup of voltage up to 12 kilovolts, while at 80% humidity the voltage is only 1.5 kV.
As little as 0.2 millijoules may present an ignition hazard; such low spark energy is often below the threshold of human visual and auditory perception.
Typical ignition energies are:
- 0.017 mJ for hydrogen
- 0.2-2 mJ for hydrocarbon vapors
- 1–50 mJ for fine flammable dust
- 40–1000 mJ for coarse flammable dust.
The energy needed to damage most electronic devices is between 2 and 1000 nanojoules.
A relatively small energy, often as little as 0.2–2 millijoules, is needed to ignite a flammable mixture of a fuel and air. For the common industrial hydrocarbon gases and solvents, the minimum ignition energy required for ignition of vapor-air mixture is lowest for the vapor concentration roughly in the middle between the lower explosive limit and the upper explosive limit, and rapidly increases as the concentration deviates from this optimum to either side. Aerosols of flammable liquids may be ignited well below their flash point. Generally, liquid aerosols with particle sizes below 10 micrometers behave like vapors, particle sizes above 40 micrometers behave more like flammable dusts. Typical minimum flammable concentrations of aerosols lay between 15 and 50 g/m3. Similarly, presence of foam on the surface of a flammable liquid significantly increases ignitability. Aerosol of flammable dust can be ignited as well, resulting in a dust explosion; the lower explosive limit usually lies between 50 and 1000 g/m3; finer dusts tend to be more explosive and requiring less spark energy to set off. Simultaneous presence of flammable vapors and flammable dust can significantly decrease the ignition energy; a mere 1 vol.% of propane in air can reduce the required ignition energy of dust by 100 times. Higher than normal oxygen content in atmosphere also significantly lowers the ignition energy.
There are five types of electrical discharges:
- Spark, responsible for the majority of industrial fires and explosions where static electricity is involved. Sparks occur between objects at different electric potentials. Good grounding of all parts of the equipment and precautions against charge buildups on equipment and personnel are used as prevention measures.
- Brush discharge occurs from a nonconductive charged surface or highly charged nonconductive liquids. The energy is limited to roughly 4 millijoules. To be hazardous, the voltage involved must be above about 20 kilovolts, the surface polarity is negative, flammable atmosphere is present at the point of discharge, and the discharge energy is sufficient for ignition. Due to maximum charge density on surface, an area of at least 100 cm2 has to be involved. Not observed as a hazard for dust clouds.
- Propagating brush discharge is high in energy and dangerous. Occurs when an insulating surface of up to 8 mm thick (e.g. a teflon or glass lining of a grounded metal pipe or a reactor) is subjected to a large charge buildup between the opposite surfaces, acting as a large-area capacitor.
- Cone discharge, also called bulking brush discharge, occurs over surfaces of charged powders with resistivity above 1010 ohms, or also deep through the powder mass. Cone discharges aren't usually observed in dust volumes below 1 m3. The energy involved depends on the grain size of the powder and the charge magnitude, and can reach up to 20 mJ. Larger dust volumes produce higher energies.
- Corona discharge, considered non-hazardous.
Read more about this topic: Static Electricity
Famous quotes containing the words energies and/or involved:
“... no one who has not been an integral part of a slaveholding community, can have any idea of its abominations.... even were slavery no curse to its victims, the exercise of arbitrary power works such fearful ruin upon the hearts of slaveholders, that I should feel impelled to labor and pray for its overthrow with my last energies and latest breath.”
—Angelina Grimké (18051879)
“I cannot exaggerate the waste of the Presidents time and the consumption of his nervous vitality involved in listening to congressmens intercession as to local appointments. Why should the President have to have his time taken up in a discussion over ... who shall be the postmistress of Devils Lake, in North Dakota? How should he be able to know ... who is best fitted to fill such a place?”