Mineral-insulated Copper-clad Cable - Disadvantages

Disadvantages

  • The termination points: While the length of the MI cable is very tough, at some point, each run of cabling terminates at a splice or within electrical equipment. These terminations are vulnerable to fire, moisture, or mechanical impact.
  • Vibration: MICC is not suitable for use where it will be subject to vibration or flexing, for example connection to heavy or movable machinery. Vibration will crack the cladding and cores, leading to failure.
  • Labour Cost: During installation MI cable must not be bent repeatedly as this will cause work hardening and cracks in the cladding and cores. A minimum bend radius must be observed and the cable must be supported at regular intervals. The magnesium oxide insulation is hygroscopic so MICC cable must be protected from moisture until it has been terminated. Termination requires stripping back the copper cladding and attaching a compression gland fitting. Individual conductors are insulated with plastic sleeves. A sealing tape, insulating putty or an epoxy resin is then poured into the compression gland fitting to provide a watertight seal. If a termination is faulty due to workmanship or damage then the magnesium oxide will absorb moisture and lose its insulating properties. Depending on the size and number of conductors, a single termination can take between 1 to 2 hours of labour. Installation of a 3-conductor MI cable (size No. 10 AWG (about 5 square mm)) takes about 65% more time than installation of a PVC-sheathed armored cable of the same conductor size. Installation of MICC is therefore a costly task. Certain PTFE, silicone or other polymer-insulated cables have been substituted in applications which require similar properties in terms of flame spread, which use less labour to terminate. MICC is still used in applications which are particularly suited to its combination of properties.
  • Voltage rating: MI cable is only manufactured with ratings up to 1000 volts.
  • Moisture absorption: The magnesium oxide insultion has a high affinity for moisture. Moisture introduced into the cable can cause electrical leakage from the internal conductors to the metal sheath. Moisture absorbed at a cut end of the cable may be driven off by heating the cable.
  • Corrosion: The copper sheath material is resistant to most chemicals but can be severely damaged by ammonia-bearing compounds and urine. A pinhole in the copper sheathing will allow moisture into the insulation, and eventual failure of the circuit. A PVC over jacket or sheaths of other metals may be required where such chemical damage is expected. When MI cable is embedded in concrete as snow melting cable it is subject to physical damage by concrete workers working the concrete into the pour. If the 3-5mil coating is damaged pin holes in the copper jacket develop causing premature failure of the snow melting system.
  • Repair: If the MI cable jacket has been damaged the magnesium oxide will wick moisture into the cable and it will lose its insulating properties causing high resistance shorts to the grounding jacket (Copper Jacket). It is often necessary to remove 2’ to 10’ of the MI Cable and splice in a new section to accomplish the repair. Depending on the size and number of conductors, a single termination can take between 1 to 2 hours of labor.

Read more about this topic:  Mineral-insulated Copper-clad Cable