Tables of AWG Wire Sizes
The table below shows various data including both the resistance of the various wire gauges and the allowable current (ampacity) based on plastic insulation. The diameter information in the table applies to solid wires. Stranded wires are calculated by calculating the equivalent cross sectional copper area. Fusing Current (melting wire) is estimated based on 25°C ambient temperature. The table below assumes DC, or AC frequencies equal to or less than 60 Hz, and does not take skin effect into account. Turns of wire is an upper limit for wire with no insulation.
-
AWG Diameter Turns of wire
(no insulation)Area Copper
resistanceNEC copper wire
ampacity with
60/75/90 °C
insulation (A)Approximate
standard metric
equivalentsFusing Current (copper) (inch) (mm) (per in) (per cm) (kcmil) (mm2) (Ω/km)
(mΩ/m)(Ω/kFT)
(mΩ/ft)Preece
(~10s)Onderdonk
(1s)Onderdonk
(32ms)0000 (4/0) 0.4600 11.684 2.17 0.856 212 107 0.1608 0.04901 195 / 230 / 260 31 kA 173 kA 000 (3/0) 0.4096 10.404 2.44 0.961 168 85.0 0.2028 0.06180 165 / 200 / 225 24.5 kA 137 kA 00 (2/0) 0.3648 9.266 2.74 1.08 133 67.4 0.2557 0.07793 145 / 175 / 195 19.5 kA 109 kA 0 (1/0) 0.3249 8.252 3.08 1.21 106 53.5 0.3224 0.09827 125 / 150 / 170 1.9 kA 15.5 kA 87 kA 1 0.2893 7.348 3.46 1.36 83.7 42.4 0.4066 0.1239 110 / 130 / 150 1.6 kA 12 kA 68 kA 2 0.2576 6.544 3.88 1.53 66.4 33.6 0.5127 0.1563 95 / 115 / 130 1.3 kA 9.7 kA 54 kA 3 0.2294 5.827 4.36 1.72 52.6 26.7 0.6465 0.1970 85 / 100 / 110 196/0.4 1.1 kA 7.7 kA 43 kA 4 0.2043 5.189 4.89 1.93 41.7 21.2 0.8152 0.2485 70 / 85 / 95 946 A 6.1 kA 34 kA 5 0.1819 4.621 5.50 2.16 33.1 16.8 1.028 0.3133 126/0.4 795 A 4.8 kA 27 kA 6 0.1620 4.115 6.17 2.43 26.3 13.3 1.296 0.3951 55 / 65 / 75 668 A 3.8 kA 21 kA 7 0.1443 3.665 6.93 2.73 20.8 10.5 1.634 0.4982 80/0.4 561 A 3 kA 17 kA 8 0.1285 3.264 7.78 3.06 16.5 8.37 2.061 0.6282 40 / 50 / 55 472 A 2.4 kA 13.5 kA 9 0.1144 2.906 8.74 3.44 13.1 6.63 2.599 0.7921 84/0.3 396 A 1.9 kA 10.7 kA 10 0.1019 2.588 9.81 3.86 10.4 5.26 3.277 0.9989 30 / 35 / 40 333 A 1.5 kA 8.5 kA 11 0.0907 2.305 11.0 4.34 8.23 4.17 4.132 1.260 56/0.3 280 A 1.2 kA 6.7 kA 12 0.0808 2.053 12.4 4.87 6.53 3.31 5.211 1.588 25 / 25 / 30 235 A 955 A 5.3 kA 13 0.0720 1.828 13.9 5.47 5.18 2.62 6.571 2.003 50/0.25 198 A 758 A 4.2 kA 14 0.0641 1.628 15.6 6.14 4.11 2.08 8.286 2.525 20 / 20 / 25 64/0.2 166 A 601 A 3.3 kA 15 0.0571 1.450 17.5 6.90 3.26 1.65 10.45 3.184 30/0.25 140 A 477 A 2.7 kA 16 0.0508 1.291 19.7 7.75 2.58 1.31 13.17 4.016 — / — / 18 117 A 377 A 2.1 kA 17 0.0453 1.150 22.1 8.70 2.05 1.04 16.61 5.064 32/0.2 99 A 300 A 1.7 kA 18 0.0403 1.024 24.8 9.77 1.62 0.823 20.95 6.385 — / — / 14 24/0.2 83 A 237 A 1.3 kA 19 0.0359 0.912 27.9 11.0 1.29 0.653 26.42 8.051 70 A 189 A 1 kA 20 0.0320 0.812 31.3 12.3 1.02 0.518 33.31 10.15 16/0.2 58.5 A 149 A 834 A 21 0.0285 0.723 35.1 13.8 0.810 0.410 42.00 12.80 13/0.2 49 A 119 A 662 A 22 0.0253 0.644 39.5 15.5 0.642 0.326 52.96 16.14 7/0.25 41 A 94 A 525 A 23 0.0226 0.573 44.3 17.4 0.509 0.258 66.79 20.36 35 A 74 A 416 A 24 0.0201 0.511 49.7 19.6 0.404 0.205 84.22 25.67 1/0.5, 7/0.2, 30/0.1 29 A 59 A 330 A 25 0.0179 0.455 55.9 22.0 0.320 0.162 106.2 32.37 24 A 47 A 262 A 26 0.0159 0.405 62.7 24.7 0.254 0.129 133.9 40.81 1/0.4, 7/0.15 20 A 37 A 208 A 27 0.0142 0.361 70.4 27.7 0.202 0.102 168.9 51.47 28 0.0126 0.321 79.1 31.1 0.160 0.0810 212.9 64.90 7/0.12 29 0.0113 0.286 88.8 35.0 0.127 0.0642 268.5 81.84 30 0.0100 0.255 99.7 39.3 0.101 0.0509 338.6 103.2 1/0.25, 7/0.1 31 0.00893 0.227 112 44.1 0.0797 0.0404 426.9 130.1 32 0.00795 0.202 126 49.5 0.0632 0.0320 538.3 164.1 1/0.2, 7/0.08 33 0.00708 0.180 141 55.6 0.0501 0.0254 678.8 206.9 34 0.00630 0.160 159 62.4 0.0398 0.0201 856.0 260.9 35 0.00561 0.143 178 70.1 0.0315 0.0160 1079 329.0 36 0.00500 0.127 200 78.7 0.0250 0.0127 1361 414.8 37 0.00445 0.113 225 88.4 0.0198 0.0100 1716 523.1 38 0.00397 0.101 252 99.3 0.0157 0.00797 2164 659.6 39 0.00353 0.0897 283 111 0.0125 0.00632 2729 831.8 40 0.00314 0.0799 318 125 0.00989 0.00501 3441 1049
In the North American electrical industry, conductors larger than 4/0 AWG are generally identified by the area in thousands of circular mils (kcmil), where 1 kcmil = 0.5067 mm². The next wire size larger than 4/0 has a cross section of 250 kcmil. A circular mil is the area of a wire one mil in diameter. One million circular mils is the area of a circle with 1000 mil = 1 inch diameter. An older abbreviation for one thousand circular mils is MCM.
Read more about this topic: American Wire Gauge
Famous quotes containing the words tables of, tables and/or wire:
“O these encounterers, so glib of tongue,
That give a coasting welcome ere it comes,
And wide unclasp the tables of their thoughts
To every ticklish reader! Set them down
For sluttish spoils of opportunity
And daughters of the game.”
—William Shakespeare (15641616)
“O these encounterers, so glib of tongue,
That give a coasting welcome ere it comes,
And wide unclasp the tables of their thoughts
To every ticklish reader! Set them down
For sluttish spoils of opportunity
And daughters of the game.”
—William Shakespeare (15641616)
“Constantly risking absurdity and death whenever he performs above the heads of his audience the poet like an acrobat climbs on rime to a high wire of his own making.”
—Lawrence Ferlinghetti (b. 1919)