Reactive Power Control
Transmission connected generators are generally required to support reactive power flow. For example on the Great Britain transmission system generators are required by the Grid Code Requirements to supply their rated power between the limits of 0.85 power factor lagging and 0.90 power factor leading at the designated terminals. The system operator will perform switching actions to maintain a secure and economical voltage profile while maintaining a reactive power balance equation:
Generator_MVARs + System_gain + Shunt_capacitors = MVAR_Demand + Reactive_losses + Shunt_reactors
The ‘System gain’ is an important source of reactive power in the above power balance equation, which is generated by the capacitive nature of the transmission network itself. By making decisive switching actions in the early morning before the demand increases, the system gain can be maximized early on, helping to secure the system for the whole day.
To balance the equation some pre-fault reactive generator use will be required. Other sources of reactive power that will also be used include shunt capacitors, shunt reactors, Static VAR Compensators and voltage control circuits.
Read more about this topic: AC Power
Famous quotes containing the words power and/or control:
“The open frontier, the hardships of homesteading from scratch, the wealth of natural resources, the whole vast challenge of a continent waiting to be exploited, combined to produce a prevailing materialism and an American drive bent as much, if not more, on money, property, and power than was true of the Old World from which we had fled.”
—Barbara Tuchman (19121989)
“A super person is one who expects to manage a career, home, and family with complete ease, expecting to maintain a perfect job, a perfect marriage, a perfect house, and perfect control of the children.”
—Joyce Portner (late 20th century)