80 PLUS - Efficiency Level Certifications

Efficiency Level Certifications

80 Plus test type 115V internal non-redundant 230V internal redundant
Fraction of rated load 10% 20% 50% 100% 10% 20% 50% 100%
80 Plus 80% 80% 80%
80 Plus Bronze 82% 85% 82% 81% 85% 81%
80 Plus Silver 85% 88% 85% 85% 89% 85%
80 Plus Gold 87% 90% 87% 88% 92% 88%
80 Plus Platinum 90% 92% 89% 90% 94% 91%
80 Plus Titanium 90% 94% 96% 91%

Redundant are typically used in data centers.

For the higher certification levels, the requirement of 0.9 or better power factor was extended to apply to 20% and 50% load levels, as well as at 100% load. The Platinum level requires 0.95 or better power factor for servers.

The Climate Savers Computing Initiative efficiency level targets for workstations for 2007 through 2011, correspond to the 80 Plus certification levels. From July 2007 through June 2008, basic 80 Plus level (Energy Star 4.0). For next year target is, 80 Plus Bronze level, the following year 80 Plus Silver, then 80 Plus Gold, and finally Platinum.

Read more about this topic:  80 PLUS

Famous quotes containing the words efficiency and/or level:

    Nothing comes to pass in nature, which can be set down to a flaw therein; for nature is always the same and everywhere one and the same in her efficiency and power of action; that is, nature’s laws and ordinances whereby all things come to pass and change from one form to another, are everywhere and always; so that there should be one and the same method of understanding the nature of all things whatsoever, namely, through nature’s universal laws and rules.
    Baruch (Benedict)

    There is only one honest impulse at the bottom of Puritanism, and that is the impulse to punish the man with a superior capacity for happiness—to bring him down to the miserable level of “good” men i.e., of stupid, cowardly and chronically unhappy men.
    —H.L. (Henry Lewis)